UniFlex

Leaders in Comfort Control and Energy Solutions.
Q-Flex & FR1, flexible duct you can depend on!
Univent Ceiling Diffuser

Adjustable Air Distribution Patterns & Ceiling Height Air Distribution Flow

Setting 1
For use with air conditioning systems that louvre panels are positioned to move the air at a shallow rate.
Setting 2
In the case of high ceilings or use with an envelope cooler the louvre panels should be inverted to achieve a deeper throw of air.
Setting 3
For a down jet effect the louvre panels should be in the inverted opposing position. This works well getting warm air to the floor.

Uni-Vents will maximise your heating and cooling system performance with less noise and lower resistance, allowing the flexibility of delivering conditioned air where and when you require it.

Performance Data Notes:

Air Throw is measured per ISO-1984 (B): The maximum distance from the centre of the core and a plane which is tangential to the 0.25m /s, and perpendicular to the intended direction of flow.

 

 Duct Type - Neck Velocity Flow (l/s) Throw (m) NR
 200 Circular - 1m/s  -  -  -
 200 Circular - 1.5 m/s  66  1  8
 200 Circular - 2 m/s  88  2.5 15
 200 Circular - 2.5 m/s 110 4.3 20
 200 Circular - 3 m/s  132 5.6 24
 200 Circular - 3.5 m/s 154 6.6 28
 200 Circular - 4 m/s 176 7.5 31
 250 Circular - 1m/s  -  -  -
 250 Circular - 1.5 m/s 122 2.4 7
 250 Circular - 2 m/s 162 4.8 13
 250 Circular - 2.5 m/s 203 6.4 19
 250 Circular - 3 m/s  244 7.8 23
 250 Circular - 3.5 m/s 284 9.2 27
 250 Circular - 4 m/s 325 10.7 31
 300 Circular - 1m/s  -  -  -
 300 Circular - 1.5 m/s 194 5.0 76
 300 Circular - 2 m/s 259 7.1 13
 300 Circular - 2.5 m/s 324 8.7 18
 300 Circular - 3 m/s  389 10.5 22
 300 Circular - 3.5 m/s 454 12.3 26
 300 Circular - 4 m/s 518 14.4 30