FBQ (Single & Three Phase)

FBQ50E
FBQ60E
FBQ71E
FBQ100E
RZQS50A
RZQS60A
RZQS71A
RZQS100A

INDOOR UNITFBQ50EVEFBQ60EVEFBQ71EVEFBQ100EVEFBQ100EVE
OUTDOOR UNIT RZQS50AV1 RZQS60AV1 RZQS71AV1 RZQS100AV1 RZQS100AY1
Rated Capacity Cool (kW) 5.0 5.8 7.1 10.0 10.0
Rated Capacity Heat (kW) 6.0 7.0 8.0 11.2 11.2
Capacity Range Cool (kW) 3.2-5.6 3.2-6.0 3.2-8.0 5.0-11.2 5.0-11.2
Capacity Range Heat (kW) 3.5-7.0 3.5-8.0 3.5-9.0 5.1-12.8 5.1-12.8
Power Input (Rated) Cool (kW) 1.35 1.59 1.99 2.73 2.73
Power Input (Rated) Heat (kW) 1.43 1.83 1.98 2.82 2.82
E.E.R / C.O.P C/H 3.70/4.20 3.65/3.83 3.57/4.04 3.66/3.97 3.66/3.97
Air Flow Rate (Rated) l/s 300 300 383 533 533
Indoor Sound Level (H) @ 1.5m dBA 35 35 38 38 38
Piping Length (m) 50 50 50 75 75
Indoor Fan Speeds H/M/L H/M/L H/M/L H/M/L H/M/L
Dimensions (HxWxD) Indoor (mm) 245 x 1000 x 800 245 x 1000 x 800 245 x 1000 x 800 245 x 1400 x 800 245 x 1400 x 800
Dimensions (HxWxD) Outdoor (mm) 770 x 900 x 320 770 x 900 x 320 990 x 940 x 320 1430 x 940 x 320 1430 x 940 x 320
Weight Indoor (kg) 37 37 37 47 47
Weight Indoor Outdoor (kg) 64 64 75 108 108
Power Supply V/Hz 1 Phase, 220-240V, 50Hz 1 Phase, 220-240V, 50Hz 1 Phase, 220-240V, 50Hz 1 Phase, 220-240V, 50Hz 3 Phase, 380-415V, 50Hz
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Refrigerant R410A R410A R410A R410A R410A
Pipe Sizes Liquid (mm) 9.5 (Flared) 9.5 (Flared) 9.5 (Flared) 9.5 (Flared) 9.5 (Flared)
Pipe Sizes Gas (mm) 15.9 (Flared) 15.9 (Flared) 15.9 (Flared) 15.9 (Flared) 15.9 (Flared)
Pipe Sizes Drain (mm) ID 25 / OD 32 ID 25 / OD 32 ID 25 / OD 32 ID 25 / OD 32 ID 25 / OD 32
Supply Air Opening mm (HxW) 176 x 792 176 x 792 176 x 792 176 x 1192 176 x 1192
Return Air Opening mm (Oval) 208 x 952 208 x 952 208 x 952 208 x 1352 208 x 1352
Outdoor Operating Range Cool (°C DB) -5 to 46 -5 to 46 -5 to 46 -5 to 46 -5 to 46
Outdoor Operating Range Heat (°C DB) -15 to 16 -15 to 16 -15 to 16 -15 to 16 -15 to 16
EPA Sound Power Level dBA 66 66 69 69 69
Outdoor Sound Level (H) @ 1m Pressure dBA (C/H) 48/50 48/50 50/52 53/55 53/55

Notes:
i. The Rated Capacity, Power Input and Running Current are measured in accordance with AS/NZS 3823.1.2
Cooling: Indoor temp: 27°CDB/19°CWB, Outdoor temp: 35°CDB/24°CWB
Heating: Indoor temp: 20°CDB/15°CWB, Outdoor temp: 7°CDB/6°CWB
ii. Indoor and outdoor sound levels are determined in an anechoic chamber and may differ once the unit is installed due to ambient conditions